CA202 Vibration 144-202-000-205
• High sensitivity: 100 pC/g
• Frequency response: 0.5 to 6 000 Hz
• Temperature range: −55 to 260 °C
• Available in standard versions and Ex versions certified for use in potentially explosive atmospheres
• Symmetrical sensor with internal case insulation and differential output
• Hermetically welded austenitic stainless-steel case and heat-resistant stainless-steel protection hose
• Integral cable
• Non-contact measurement system based on eddy-current principle
• Ex certified versions for use in hazardous areas (potentially explosive atmospheres)
• Conforms to API 670 recommendations
• 1, 5 and 10 m systems
• Temperature-compensated design
• Voltage or current output with protection against short circuits
• Frequency response: DC to 20 kHz (−3 dB)
• Measurement range: 2 or 4 mm
• Temperature range: −40 to +180 °C
• Voltage output signal: 100 or 500 mV/ g
• Frequency response:
0.5 to 14 000 Hz (100 mV/ g versions)
0.2 to 3 700 Hz (500 mV/ g versions)
• Temperature range:
−55 to 120 °C (100 mV/ g versions)
−55 to 90 °C (500 mV/ g versions)
• Isolated electronics with internal shield for reduced noise and improved bias-voltage stability
• Ground isolated from case
• Available as a sensor only or with an integral cable
• Available in standard versions and Ex versions certified for use in hazardous areas
• 16 individually configurable dynamic channels
• 16 parallel programmable anti-aliasing filters and ADCs
• First 4 channels also configurable as tacho inputs
• Last 12 channels also configurable as process values
• VME architecture
• Configurable Synchronous and Asynchronous sampling
• High resolution 3200- line FFT
• 10 fully configurable frequency bands per channel
• 6 configurable alarms per band with hysteresis deadbands
• Schedule, ‘on-alarm’ and ‘on exception’ based logging
• Ethernet and Serial RS-485 communication options
• On-board buffer storage
• Status indication by 3-colour LED on front panel
• Live insertion / removal of cards with automatic configuration
•16 channel interface card for CMC 16 (Condition Monitoring Card)
• Screw terminal strip (48 terminals)
• Ensures EMI protection for all inputs and outputs
• Provides signal conditioning for all inputs
• First 4 channels can be selected as tacho or dynamic inputs (i.e. vibration)
• Last 12 channels can be selected as dynamic or process inputs
• Channel 16 can be selected as dynamic, process or cold junction compensation input for thermocouples
• Inputs can be routed via VM 600 Raw Bus and Tacho Bus
• On-board isolated Serial RS-485 communication option
• Live insertion / removal of cards
-For CA piezoelectric accelerometers and CP dynamic pressure transducers
-Configurable high-pass and low-pass filters
-Frequency range: 0.5 Hz to 20 kHz
-Optional integrator to give a velocity output
-Optional 2-wire current or 3-wire voltage transmission
-Certified for use in potentially explosive atmospheres
-A range of installation options are available